Cummins, Inc. (Cummins) is recalling certain 2020-2022 Cummins Power Generation C500D6Re trailer-mounted generator sets (gensets). Incorrect logic in the output box door switch may cause the gensets to not shut down as intended when operated in parallel with other gensets.
Consequence & remedy
Consequence: The operator may be unaware that the gensets did not shut down, which could result in burns, electrical shock or arc flash, increasing the risk of injury.
Remedy: Cummins will repair the electrical circuit, free of charge. Owner notification letters were mailed August 22, 2022. Owners may contact Cummins customer service at 1-800-286-6467.
Cummins Inc. (Cummins) is recalling certain 2019-2021 Power Generation C70D2RE and C100D2RE trailer-mounted generator sets. Certain Molded Case Circuit Breakers (MCCBs) may have been manufactured improperly, which can result in inadequate circuit protection.
Consequence & remedy
Consequence: Inadequate circuit protection can increase the risk of personal injury or fire.
Remedy: Cummins will inspect and replace the circuit breakers, as necessary, free of charge. Owner notification letters were mailed January 14, 2022. Owners may contact Cummins customer service at 1-800-286-6467. Cummins number for this recall is C4776.
Model-level recall history does not show whether a particular VIN is affected or has received a repair. Check a VIN with NHTSA ↗